One Shot Universal Liquid Treat
It is a well - balanced blend for boiler water treatment products, resulting in a scale and corrosion control by one shot operation. A unique one-step Boiler treatment liquid to control the formation of rust and scale in low pressure and auxillary boilers with working pressure up to 20 bars.
Control is by simple boiler water tests or RX CLEANSERS can provide a suitable test kits for this purpose.
Used in low pressure and auxillary boilers
:::::::::::::::::::::Alkalinity TEST FOR BOILER & COOLING WATER ::::::::::::::::::::::::
REAGENT & APPARATUS :
Reagent: RXSOL TK 7 , TK 8 , TK 9 , . Apparatus : TEST TUBE , Titrator or DROPPER
PROCEDURE for p-ALKALINITY test ( STEP WISE ):
- Measure 10 ml of SAMPLE WATER in graduated TEST TUBE / CYLINDER
- Add 1-2 drops of RXSOL TK7 and mix with the stirring rod , If sample turns red / PINK ( which indicates presence of p-Alkalinity ) then follows 3rd step otherwise if sample remains colourless ( Record p-Alkalinity = 0 ) .
- Add RXSOL TK9 drop by drop ( by counting ) , mixing with the stirring rod until colour just disappears. Each drop is equivalent to 25 ppm of p-Alkalinity , expressed as CaCO3
RESULT : Each DROPS is equivalent to 25 PPM of Alkalinity .
NOTE : p-Alkalinity VALUE = 25 X ( Total Number of DROPS of TK9 , during 3rdstep )
PROCEDURE for p-ALKALINITY & TOTAL ALKALINITY ( STEP WISE ):
- Measure 10 ml of SAMPLE WATER in graduated TEST TUBE / CYLINDER
- Add 1-2 drops of RXSOL TK7 and mix with the stirring rod , If sample turns red / PINK ( which indicates presence of p-Alkalinity ) then follows 3rd step otherwise if sample remains colourless ( Record p-Alkalinity = 0 ) then proceed to STEP- 4.
- Add RXSOL TK9 drop by drop ( by counting ) , mixing with the stirring rod until colour just disappears. Each drop is equivalent to 15 ppm of p-Alkalinity , expressed as CaCO3
- Add 2-3 drops of RXSOL TK8 and mix with stirring rod , the sample will turn to BLUISH-GREEN .
- AddRXSOL TK9 carefully by counting drop by drop and mixing throughly until a light reddish pink colour develop.
RESULT : Each DROPS is equivalent to 25 PPM of Alkalinity .
NOTE : p-Alkalinity ppm CaCO3VALUE ( A ) = 25 X ( Total Number of DROPS of TK9 , during 3rdstep )
Total Alkalinity ppm CaCO3VALUE = A + { 25 X ( Total Number of DROPS of TK9 , during 5th step )}
NUMBER OF DROPS OF TK9 p-Alkalinity as CaCO3
1 >>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>25
3 >>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>> 75
5 >>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>> > 125
20 >>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>> > 500
40 >>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>> 1000
Optimum Result : p-Alkalinity level is between 100 to 150 PPM is suggested. For Below 50 ppm , Dose ½ Ltrs of RXSOL-50-5001-020for 1000 Ltrs of BOILER WATER , to maintain p-Alkalinity level 100 ppm. Refill pack : REPLACEMENTS TK7 : ECONOMIC PACK ( 100 / 200 / 500 ml ) available TK8 : ECONOMIC PACK ( 100 / 200 / 500 ml ) available TK9 : ECONOMIC PACK ( 100 / 200 / 500 ml ) available |
For Tank cleaning operation pl. click here to know more................
OTHER VALUABLE PRODUCTS
18 / 25 / 35 / 210 Ltr.
CHARACTERISTIC :
- Convenient liquid treatment, which provides the basic alkalinity on which successful water treatment depends.
- Provides optimum conditions for hardness control to function.
- Neutralizes acid conditions.
- Will assist in keeping silica in suspension.
- Simple test to determine level of treatment.
- Can be used in boilers of all pressures.
- Can be used as a neutralizer after acid cleaning operations
- Suitable for use with all auxiliary boilers; waste heat units; economizers, package boilers, smoke and water tube boilers.
- Dispersant action suspends sludge and sediment particles for efficient blow down.
- Oxygen scavenging for optimum protection.
- Protects boiler, steam lines, condensate lines and feed water lines from corrosion.
- Fast action due to catalyst.
- Simple test to determine level of treatment.