EcoGuard Corrosion Protection PolyPhos

← Back to all products
Cooling Water Chemical-43

EcoGuard Corrosion Protection PolyPhos

SKU: RXSOL-43-4029-025
Corrosion and Scale Inhibitor with Phosphates and Polyphosphates.
Pack Size / Specification:
Corrosion Inhibitor for Open Cooling Circulating System available in 25 Kg packing.
Enquire About This Product →

Technical Specifications

Property Value
Appearance Clear to slightly hazy amber liquid
Odor Mild characteristic
pH (as supplied) Alkaline
Specific Gravity @ 25°C 1.10 – 1.20
Solubility Fully water soluble
Freeze Point Below 0°C
Shelf Life 12 months (sealed container)

Application & Dosage

Corrosion Inhibitor OPEN Cooling System  scientifically formulated to keep clean open recirculating systems  and also prevent from scale formation . Chemically Corrosion Inhibitor OPEN Cooling System  will disperse scale and corrosive products, silt etc and can be used as an anti-foulant along with other treatments. 

Excellent scale inhibition for a variety of applications including cooling circuits, boilers and RO units.

It is widely used in Boilers, cooling water and membranes

Dosage

 
System Type Typical Dosage
Open Loop Cooling Towers 50 – 150 ppm in recirculating water
High-corrosion conditions Up to 200 ppm based on metallurgy and water quality
pH Control Range Operates best between pH 7.0 – 8.5
  • Dosing Method: Continuous injection via dosing pump into cooling water basin or line.
  • Monitoring: Maintain residual phosphate at 2–5 ppm and zinc at 0.5–1.5 ppm in system water

  • Compatible with: Sodium hypochlorite, non-oxidizing biocide: RXSOL-40-4009-025, anti-scalants: RXSOL-33-3302-025.