EcoGuard Corrosion Protection PolyPhos
Corrosion Inhibitor for Open Cooling Circulating System available in 25 Kg packing.
Technical Specifications
| Property | Value |
|---|---|
| Appearance | Clear to slightly hazy amber liquid |
| Odor | Mild characteristic |
| pH (as supplied) | Alkaline |
| Specific Gravity @ 25°C | 1.10 – 1.20 |
| Solubility | Fully water soluble |
| Freeze Point | Below 0°C |
| Shelf Life | 12 months (sealed container) |
Application & Dosage
Corrosion Inhibitor OPEN Cooling System scientifically formulated to keep clean open recirculating systems and also prevent from scale formation . Chemically Corrosion Inhibitor OPEN Cooling System will disperse scale and corrosive products, silt etc and can be used as an anti-foulant along with other treatments.
Excellent scale inhibition for a variety of applications including cooling circuits, boilers and RO units.
It is widely used in Boilers, cooling water and membranes
Dosage
| System Type | Typical Dosage |
|---|---|
| Open Loop Cooling Towers | 50 – 150 ppm in recirculating water |
| High-corrosion conditions | Up to 200 ppm based on metallurgy and water quality |
| pH Control Range | Operates best between pH 7.0 – 8.5 |
- Dosing Method: Continuous injection via dosing pump into cooling water basin or line.
-
Monitoring: Maintain residual phosphate at 2–5 ppm and zinc at 0.5–1.5 ppm in system water
- Compatible with: Sodium hypochlorite, non-oxidizing biocide: RXSOL-40-4009-025, anti-scalants: RXSOL-33-3302-025.