Physical Properties

Empirical Formula   C4H11NO
Molecular Wt   89.1
  DEHA 98% DEHA 85%
Sp. Gr. at 20°C  0.855 - 0.875 0.895 - 0.905
Refractive Index 1.418 - 1.420 1.418 - 1.420
Boiling Point 124 to 126°C 94 to 96°C
Freezing Point -25 to -27°C Below 0°C
Flash Point (Closed C) Below 45°C 45 to 47°C
Solubility in water Soluble Soluble
pH 10.2 10

 Specification :

Specification DEHA 98% DEHA 85%
Purity as DEHA (wt. %) 98.00 min.   85.00 min.
Water Content (% by wt.)   -- 15.00 max
Ethylamines (% by wt.) 0.5 max. 0.05 max.

 

Typical Technical Specifications

Parameter

Typical Value

Appearance

Clear, colourless to pale yellow liquid

Chemical Name

N,N-Diethylhydroxylamine

CAS Number

3710-84-7

Molecular Formula

C₄H₁₁NO

Active Concentration

85% DEHA or formulated aqueous solutions

Molecular Weight

89.14 g/mol

Solubility

Miscible with water

Function

Oxygen scavenging and corrosion control

Application

Boiler feedwater and steam-condensate systems

These specifications are indicative. Commercial DEHA oxygen scavengers are available at different active concentrations, including diluted boiler-treatment formulations.

Application & Dosage

It is use for Water Treatment Chemical, Corrosion Inhibitor, Polymerization, Photographic Chemicals, Decolourisation, etc.

DEHA used as a volatile oxygen scavenger and reacts in a ratio of 2.8/1 DEHA/O2.

RXSOL Product DEHA

RXSOL DEHA Oxygen Scavenger 25%

DEHA-based liquid oxygen scavenger for boiler feedwater treatment, dissolved oxygen control, metal passivation and steam-condensate corrosion protection.

DEHA Oxygen Scavenger, Diethylhydroxylamine Water Treatment, Boiler Oxygen Scavenger, DEHA 25% Solution, Volatile Oxygen Scavenger, Boiler Feedwater Corrosion Inhibitor, DEHA Chemical Supplier India UAE Oman.

Recommended Dosage

Parameter

Typical Starting Guidance

Theoretical DEHA requirement

1.24 ppm per 1 ppm O₂

Practical active DEHA dosage

2–3 ppm per 1 ppm O₂

DEHA residual target

Often 0.5–1.0 ppm, program-dependent

Recommended injection point

Deaerator storage section or feedwater line

Dosage control

Dissolved oxygen and DEHA residual testing

 

Application Area of DEHA :  

Water Treatment , Polymerization, Photographic Chemicals, Decolourisation , Inhibitors, Silicon Rubber
 

Example Dosage Calculation

For boiler feedwater containing 0.1 ppm dissolved oxygen:

  • Feedwater volume: 10,000 litres

  • Dissolved oxygen: 0.1 mg/L

  • Practical starting dosage: 3 mg active DEHA per mg O₂

  • Required active DEHA: 3 grams

  • Required 25% DEHA solution: 12 grams

This is an illustrative oxygen-demand calculation, excluding any additional requirement for maintaining the specified DEHA residual.