Corrosion Inhibitor for Diesel Cooling Water Treat
Corrosion Inhibitor for Diesel Cooling Water Treatment - RXSOL CIDC is a unique formulation with organic Corrosion Inhibitors, Anti-Scalant for use in closed cooling water systems, for preventing corrosion and scale Formation in Internal combustion engines, compressor cooling system, DG -set at high or low temperature. It is a concentrated liquid, also used as a corrosion inhibitor ( Protects all the metals including cast iron, mild steel, copper .)
The stable oxide film that is formed by RXSOL CIDC prevents corrosion caused by the electrolytic action between dissimilar metals used in the system .RXSOL CIDC has been field tested and found to have no detrimental effects on non-metallic substances such as seals, glands, packing, hoses, gaskets etc., normally used in these’ systems.
Application-Dg*
Sets Internal combustion engines closed circuit cooling system compressor cooling system. RXSOL CIDC incorporates superior corrosion inhibitors to prevent corrosion works by free of scale deposits.
Initial dosage for an untreated system is 9 litres of RXSOL CIDC / 1000 litres of untreated distilled water. This will bring the treatment up to the minimum level of 1000 ppm nitrite. For best result and prolonged engine life add RXSOL CIDC every 500 -6500 km. or 250 to 300 hours of running time or every 2 month interval.
In cases where systems are contaminated with oil and/or scale, they should be cleaned before starting to apply RXSOL CIDC.There are suitable RX BRAND products to carry out the cleaning. Degreasing should be carried out using RXSOL-20-2002-025 and descaling by using RXSOL 1008.
SPECIFICATION / HANDLING
Color : Odour Pink/ red (Colour changes of the product cannot be excluded the effects will however not impaired.)
Sp. Gravity : 1.1 to 1.25
pH : Alkaline (11.3 – 11.5)
None. Rxsol-2000 is an alkaline product & should be handled like other chemical Avoid contact with Eyes, Skin, in case of contact, wash with copious amounts of water immediately.
Freezing Point - 17 0 c
Nitrite (as PPM NO2) 0 100-200 300-600 700-900 1100-1300 1440-2400
RXSOL CIDC /1000L 13.0 11.3 8-10 5-7 1.5-3.5 0
METHOD OF USE
1. Properly clean the system with water and alkaline liquid, if necessary.
2. Add 0 .15-1.5 % of RXSOL CIDC in the system or recommended Nitrite level 1400 – 2500 ppm can be measured and controlled by any standard RXSOL test kit for Nitrite, Chloride test also helps to detect excess contamination to maintain acceptable levels. when the product is dosed as recommended limit By buffering action of RXSOL CIDC, pH should be maintained between 8.3 and 10 by the treatment.